Product Overview

  • Targets reactive compounds and volatile organic compounds
  • Removes toxic and impure gases by physical adsorption
  • Suitable for use in commercial and industrial applications
  • Accurate service life testing
Max. Operating Temperature
  • -20˚C - 50˚C
Relative humidity
  • 10-95%

Engineered Media

SAAFBlend™ GP engineered gas removal chemical media is designed to efficiently remove gaseous contaminants from airstreams.

SAAFBlend™ GP is produced from an equal volumetric mix of SAAFOxidant™ and SAAFCarb™ media. Manufactured from spherical and porous pellets, SAAFOxidant™ engineered media is composed of a combination of activated alumina and other binders. Potassium permanganate is impregnated in this media combination in order to provide optimum adsorption, absorption and oxidation of various gaseous contaminants. Potassium permanganate is applied uniformly during pellet formation and is distributed throughout the pellet volume. This process provides the maximum amount of impregnant for chemical reaction and optimal performance. SAAFCarb™ media is manufactured from pelletised activated carbon media that is composed of high-quality virgin substrates, in order to provide optimum adsorption for various gaseous contaminants.

Adsorptive Process

The SAAFCarb™ media removes toxic and impure gases by physical adsorption. In this process, the gases remain on the surface of the pellet.

Chemisorptive Process

The SAAFOxidant™ media chemisorptive process removes the contaminant gases by adsorption, absorption and chemical reaction. The gas is therefore trapped within the pellet, where oxidation changes the gases into harmless solids, thereby mitigating the possibility of desorption.

Quality Control

SAAFBlend™ GP media contains an equal volumetric mix of SAAFOxidant™ and SAAFCarb™ media. Each media undergoes respective quality control tests.

Packaging Options

SAAFBlend™ GP media is packaged in 500 kg big bag. SAAFBlend™ GP media is also available packaged in SAAF cartridges, cassettes and trays.

Application Guidelines

SAAFBlend™ GP media performs under the following application guidelines (actual capacities and efficiencies may vary):

  • Temperature: -20° to 50°C
  • Humidity: 10% – 95% RH
  • Suitable for use in commercial and industrial systems with equipment face velocities from 0.25 - 2.5 m/s).

Refer to appropriate AAF documentation for additional information on contaminant gases.

Installation and Disposal Requirements

The installers must use dust masks, safety goggles and rubber gloves. The spent SAAFBlend™ GP media must be disposed of according to local and national guidelines.

Safety

Wet activated carbon adsorbs atmospheric oxygen, causing low oxygen supply in enclosed areas or packed containers. This can be potentially hazardous for workers who enter these oxygen-depleted areas. Make sure that the workers adhere to the local and national safety guidelines.

Any Questions?